VIBROMAT or VIBROMAT SM
Vibration isolation supports for equipment.
Fibromata designed for use in vibrator for engineering equipment.
Each vibromat depending on the type has a steel plate and a polyurethane elastomer Sylomer.
Used for vibration isolation of the following elements:
There are several types of Vibromatic:
Type A, b and C differ only in the thickness and structure of most supports.
Type a – the thickness of the protective layer 25 mm metal plate located on top of the isolator. Size 150*150 mm.
Type In the thickness of 50 mm, has an upper metal plate and lower with holes for additional fastening to the floor. Base size 250*150 mm. the Top plate 150*150 mm.
Type With thickness of 75 mm,the upper and lower metal plates the size of the elastomer. Size 150*150 mm.
To choose the desired thickness, it is necessary to know the minimum rpm:
After selecting the thickness, look in the table the maximum load that will fall on 1 support.
We will help You to calculate and choose the right Vibromat for your hardware.
Type Fibromata |
Name |
Load, kg |
The natural frequency under load, Hz* |
Sludge under load, mm* |
|||
min |
max |
min |
max |
min |
max |
||
A |
Vibromat SM 60/25 |
35 |
61 |
23.8 |
13.3 |
0.7 |
1.6 |
Vibromat SM 120/25 |
48 |
119 |
24.7 |
12.3 |
0.6 |
1.8 |
|
Vibromat SM 250/25 |
100 |
246 |
20.2 |
10.7 |
0.8 |
2.3 |
|
Vibromat SM 470/25 |
198 |
465 |
18.4 |
10.3 |
0.9 |
2.5 |
|
Vibromat SM 940/25 |
329 |
923 |
17.7 |
10 |
1 |
3 |
|
B |
Vibromat SM 60/50 |
35 |
59 |
16.2 |
9.2 |
1.4 |
3.1 |
Vibromat SM 120/50 |
48 |
110 |
16.9 |
9 |
1.2 |
3.3 |
|
Vibromat SM 250/50 |
100 |
226 |
13.8 |
7.7 |
1.7 |
4.5 |
|
Vibromat SM 470/50 |
198 |
392 |
12.1 |
7.4 |
2 |
4.7 |
|
Vibromat SM 940/50 |
329 |
794 |
11.7 |
7.1 |
2.2 |
5.6 |
|
C |
Vibromat 60/75 SM |
35 |
58 |
13 |
7.5 |
2.2 |
4.5 |
Vibromat SM 120/75 |
48 |
107 |
13.6 |
7.4 |
1.9 |
4.9 |
|
Vibromat SM 250/75 |
100 |
214 |
11.1 |
6.5 |
2.5 |
6.3 |
|
Vibromat SM 470/75 |
198 |
349 |
9.7 |
6.5 |
3.1 |
6.1 |
|
Vibromat SM 940/75 |
329 |
722 |
9.3 |
5.9 |
3.4 |
7.9 |
INSTALLATION:
The anti-vibration mounts are mounted through the top plate using the M12 thread. Fastening member having inside threads and screwed, not reaching the end of the elastomer thickness of 10 mm.
The surface on which are mounted anti-vibration mount must be smooth.
A support placed under the equipment to provide uniform distribution of loading equipment at the base.